Electrical | |
Nominal Input Voltage | 100 – 240 VAC |
Maximum Input Current | 32A(Max) |
Input Frequency | 50-60 Hz |
Input Connection | For G Plug : IEC 60309 32A |
Input Power | 7360 VA(Max) |
Outlet Type | Total: 21 x IEC320 C13 + 3 x IEC320 C19 Bank1-1: Outlet 1 – 8; 7 x C13 + 1 x C19 Bank1-2: Outlet 9 – 16; 7 x C13 + 1 x C19 Bank2: Outlet 17 – 24; 7 x C13 + 1 x C19 |
Nominal Output Voltage | 100 – 240 VAC |
Maximum Output Current (Outlet) | C13: 10A(Max) C19: 16A(Max) |
Maximum Output Current (Bank) | 16A(Max) |
Maximum Output Current (Total) | 32A(Max) |
Breakers | 2 x 16A UL489 Breaker |
Metering | Bank Level Current, Voltage, VA , PF and kWh Monitoring |
Outlet Switching | None |
Environment Sensor Ports | 2 |
Metering Accuracy | Voltage Range : 100VAC ~ 250VAC +/-1% Power Range : 100W ~ Maximum Capacity +/- 2% Current Range : 0.1A~1A +/- 0.1A, 1A~20A +/-1% |
Physical Properties | |
Dimensions (L x W x H) | 177.50 x 6.60 x 4.40 cm (69.88 x 2.6 x 1.73 in.) |
Weight | 5.82 kg ( 12.82 lb ) |
Power Cord Length | 1.6 m |
Environmental | |
Temperature (Operating / Storage) | 0–40°C / -20–60°C |
Humidity (Operating & Storage) | 0–80% RH, Non-Condensing |
Compliance | |
EMC Verification | CE, C-Tick, Others by Request |
Safety Verification | TUV-CB, GOST, Others by Request |
Note For some of rack mount products, please note that the standard physical dimensions of WxDxH are expressed using a LxWxH format. |